EasyManua.ls Logo

Trox FKRS-EU - Installation: Lightweight Partition Walls (Dry Mortarless Fire Batt Details); Performance Class and Installation Details

Trox FKRS-EU
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Performance class and installation details
Perform-
ance class
Fire batt Casing construction /
DN [mm]
Distance to
load-
bearing
structural
elements
[mm]
Distance between two fire dampers
[mm]
Galvanised
steel
Stainless
steel
Two installation
openings
One installation
opening (flange to
flange)
EI 120 S HENSEL 100...200 75 200
EI 120 S Hilti 100...200 75
EI 90 S Hilti 100...315 100...200 40 200 a = 40...400
EI 90 S HENSEL 100...315 40
Personnel:
Specialist personnel
Materials:
Fire batt systems
Ä
‘Acceptable fire batt systems’ on page 14
Requirements
Performance class EI 120 S or EI 90 S
Ä
‘Performance class and installation details ’ Table on page 35
Lightweight partition walls with metal support structure and cladding on both sides, W ≥ 100 mm; detailed specifi-
cation
Ä
on page 27.
Duct connection with flexible connector (recommended)
1. Erect the lightweight partition wall according to the manufacturer's instructions and create an installation
opening
Ä
27.
2.
Push the fire damper into the wall opening and fix it with threaded rods
Ä
46.
3. Extend the fire damper on the installation side with an extension piece (either attachment or supplied by
others).
Note
The fire damper must have a fire protection coating (50 mm) on the installation side. The spigot of the fire
damper must not be coated. This is why the fire damper requires an extension piece on the installation
side; alternatively, the fire damper can be connected to the ductwork before the coating is applied.
4. Completely close off the perimeter gap between the fire damper and the wall or ceiling slab with two layers of
coated mineral wool slabs, ≥ 140 kg/m³. Apply fire protection sealant to the cut faces of the mineral wool slabs
and fit them tightly into the opening. Seal any gaps between the mineral wool slabs and the trim panels, gaps
between the cut faces of cut-to-size pieces, and gaps between slabs and the fire damper by applying fire pro-
tection sealant.
5. Apply fire protection coating to joints, transitions, and any imperfections on the pre-coated mineral wool slabs.
6. Apply fire protection coating, at least 2.5 mm thick, to the fire damper casing perimeter on both sides of the
wall or ceiling slab. The actuator and release unit must not be coated.
Installation
Lightweight partition walls > Dry mortarless installation with fire batt
Fire damper Type FKRS-EU 35

Table of Contents

Other manuals for Trox FKRS-EU