7 Commissioning
After connecting and switching on the power supply, the device is automatically ready for op-
eration.
The analog and switching outputs have a 300 ms readiness delay.
7.1 Activating IO-Link mode
NOTE
The voltage range in IO-Link mode is 18…30 VDC.
Set a cycle time of min. 2.3 ms on the IO-Link master.
a The device is operational. After a readiness delay of 450 ms, the process data can be sent
to the IO-Link master.
7.2 Activating SIO mode
Connect the device to a standard I/O port or an analog port.
a The device is operational after a readiness delay of 500 ms.
The readiness delay in SIO mode is required to operate preactivated sensors so that the sensor
can exclude being connected to an IO-Link master. The readiness delay does not have an effect
on any potential IO-Link communication.