F4000 LCD Operator's Manual Document No: LT0117
System Specifications
Page 3-2 19 April 2002 Issue 2.38
3.1 SYSTEM CAPACITY
Input Circuits - Up to 508
Circuit Detector Load - 2.5mA for Active EOL (FP0472 ADR)
(MAX) - 4.0mA for Active EOL (FP0523 ADR)
- 4.0mA for Active EOL (FP0755 ADR-M)
- 120µA for Passive 39K EOL
Display Zones - Up to 528
Input to Zone Map - Freely Programmable
Control Outputs - Up to 508 plus Master Ancillary Relay
Maximum Responders - 127
Remote Display Units - Up to 8 (additional mimics allowed)
Maximum Zones per Unit - 64-192 in 19" cabinets (256 in Extender)
Other Inputs - Supervised MCP on cabinet (not large 19" cabinets)
FIP Relays - Master Alarm (MAF) (2 OFF), Fault, Standby,
Isolate, Bells, Ancillary
Relay Ratings - FIP: 2A at 30 VDC
RRM: 1A at 30 VDC
Serial Port - Programmer Terminal/Printer
Serial Port Protocol - XON/OFF 300,1200,9600 baud, 8 bits, no parity
Other Ports - RZDU, Spare and Network
Port Protection - All to AS1603.4 1987 Admt 1 & 2
Communications Loop - 4 Wire (24 VDC, 0 VDC, TX, RX)
- O/C and S/C Fault Tolerant
Alarm Response Time - 3.8 seconds MAX (127 Logical Responders)
History Log - 900 events
Printer Buffer - 170 events
Mimic Driver - ALARM LEDs