Document No: LT0117 F4000 LCD Operator's Manual
Operating Instructions - System Functions
Issue 2.38 19 April 2002 Page 6-21
6.13 GLOBAL ISOLATE
6.13.1 FUNCTION
To issue an FFCIF type 2 Global Isolate, to isolate all un-isolated zones in alarm (if any) and
to signal ISOLATE to the output logic.
6.13.2 OPERATING SEQUENCE
To issue a global isolate from a base or information recall display, other than a Zone Recall,
press:
6.13.3 NOTES
(1) This command can be accessed from any base display or data recall display except
for zone recalls.
Press the "CLEAR" key to exit from a Zone Recall display before entering the Global
Isolate command.
(2) The Global Isolate command will result in all unisolated zones in alarm being
isolated. This may result in events being removed from the FFCIF Alarm List.