30
Error
code
Symptom Error
occurs
Events during error Comments on error code
1
Temperature sensor
in the room not con-
nected or faulty
During
operation
Operation interrupted. Emptying of
the steam production source takes
place 1 hour after the error occurred.
Is the sensor intact? Is it giving an incorrect value? Resistan-
ce measurement should show approx. 10kΩ at 25˚C and
approx. 677 Ω at 100˚C.
At off
Only the error code is shown. Steam
production source does not empty.
2
Temperature sensor
in the room not con-
nected or faulty
During
operation
The standby steam room with its
steam production & Tylarium stop
working and emptying takes place
1 hour after the error occurred. The
steam room only notifi es that there is
an error. Operation is not interrupted
and emptying takes place as normal
1 hour after the steam bath ends.
Is the sensor intact? Is it giving an incorrect value? Resistan-
ce measurement should show approx. 10kΩ at 25˚C and
approx. 677 Ω at 100˚C. This sensor must be changed if it is
faulty, otherwise the standby function of the system cannot
be used.
At off
Only the error code is shown. Empty-
ing does not take place.
4
The level electrodes
in the steam tank are
short-circuited
During
operation
Operation is interrupted and error
code clearing takes place immedi-
ately.
About 5 seconds of continuous failure is required to trigger
an error code. Check that the electrode pins are touching the
electrode tube or alternatively the cables. Error code may
be triggered by water with a high concentration of salt or
minerals that increases electrical conduction and makes the
circuit board believe that the electrodes are short-circuited.
In that case clean/descale the water tank and the electrode
pins.
At off
Error code clearing takes place
immediately.
5
The steam tank over-
full level electrodes
are not working.
During
operation
Operation is interrupted and error
code clearing takes place immedi-
ately.
The uppermost, high (H) electrode has not detected the
water level within the preset time, refer to the fi lling time
in the confi guration menu. Insuffi cient water fl ow? Is the
incoming water switched on? Is there a gap in the electrode
wire connections GND/high? Grease on the coating surface
of the electrode pins? If there is no fault present at the water
connection, the value for the water level can be checked in
the confi guration menu status during restarting, to check that
the level has changed from low to mid/high during fi lling. If
the level has not changed at all from low, both the mid and
high (M, H) pins are faulty. If the level has only changed to
mid, it is only the high pin (H) that is faulty
At off
The error code cannot be triggered
when off , operation must be started
for the incoming water feed to open.
6
Contact lost with the
heater network con-
trol panel node.
During
operation
Operation is interrupted and restar-
ting takes place. For steam produc-
tion, emptying takes place immedi-
ately after restarting is completed in
case there is water in the tank.
Poor wiring connection? Check by removing and refi tting the
RJ10 connector. Check that one of the pins in the female
RJ10 connector on the circuit board or control panel may
have become misaligned or displaced, so that contact with
the connected RJ10 cable has been lost.
At off
Reboot. For steam production,
emptying takes place immediately
after rebooting is completed in case
there is water in the tank.
8
The steam tank has
overheated
During
operation
Operation is interrupted and error
code clearing takes place immedi-
ately.
The sensor at the NTC input has detected excessively high
temperature in the water tank. Check the steam pipe along
its length, and its dimensions. Check that the NTC is intact.
Resistance measurement should show approx. 10kΩ at 25˚C
and approx. 677Ω at 100˚C. Also check the water quality
and that automatic emptying is activated, so that the level
electrodes are not misleading the system due to foam in the
tank so that they believe that suffi cient water is available.
At off
Cannot be triggered when the system
is off .
10
Contact with the add-
on board has been
lost.
During
operation
Operation interrupted. In a Tylarium
emptying of the steam secondary
is taking place 1 hour after the fault
occurred.
Try restarting the system. Check by removing and refi tting
the RJ10 connector. Check that one of the pins in the female
RJ10 connector on the circuit board may have become misa-
ligned or displaced, so that contact with the connected RJ10
cable has been lost. Check the screw terminal connections
on the sensor circuit board. Alternatively change the tempe-
rature/humidity sensor that is connected to the RS485 input.
At off
Only the error code is shown. In
a Tylarium emptying of the steam
secondary is not taking place.
11
There is a fault in
the emptying of
water from the steam
tank. Switch off the
power and perform
servicing.
During
operation
Fault detected during the actual
emptying sequence of the system.
Error code clearing, Automatic
emptying, Voltage connection to the
system and water in the tank and
emptying after session completed.
Water level in the tank has been at least mid-level when
checking the tank is empty, carried out at all emptying
cycles. It must always be at its low level. Check, is the
water tank drain blocked? Is the emptying valve operating
and opening? Is the relay on the relay board that controls
the emptying valve closing? The fault may also be caused
by the high electrode pin sensing the value as water at the
same time as the mid not sensing water, the same as the
error code (level electrodes not working, mid failure) thereby
sending unknown water level.
At off
Fault detected during the actual
emptying sequence of the system.
Error code clearing, Automatic
emptying, Voltage connection to the
system and water in the tank and
emptying after session completed.
Error codes
Tampering with the device may only be performed by qualifi ed personnel