10.D/A CONVERTER
72
10. D/A CONVERTER
The D/A converter analog output can be selected from the voltage output and the current
output.
Please depending on the request at the time of order.
10-1. Voltage Output
(Depending on the request at the time of order.)
This converter is used to obtain an analog output which is linked with the indicated value
of the F340A.
The range of the analog output is from -10 to +10V.
An analog output from -10V to +10V can be obtained with respect to any digital values
set by the D/A zero setting and the D/A full scale setting functions.
The output circuit and the main circuit are isolated.
Voltage output :-10 to +10V (load resistance; 2kΩ or more)
D/A conversion speed :100 times/sec.
Resolution :1/6000
Over range :-11.0 to +11.0V
Terminals for obtaining voltage
signal.
“+” is for signal, and “-” is for
ground.
-10 to +10V can be obtained.