Installation
01/21 FlowTimer+ Set 21
The pressure (measured at the filter outlet) must always be
greater than 1 bar!
If you use a filter and / or a softening system, we
strongly recommend to monitor them directly for water
leakage using FlowTimer+ Detect V2.
In the event of a fault, the water supply is then immediately
interrupted!
Fig. 6.4.2: Pressure sensor installation after filter / regulator