Fault codes and software
email: service@vacon.com Tel: +358 (0)201 212 575 Fax: +358 (0)204 335 091
33
4
• The support and card description for new option board OPTAL. The option board
contains 6 pcs of 42...240VAC digital inputs in addition to 2AI, 2AO, 1DO.
• More information will be updated in the next release of option board manual.
• Note: The new parameters for the option boards will be supported with NC Drive
newer than version 2.0.10.
10. 3. 2. 14. NXS00001V173
Replaced version: NXS00001V172.VCN
System software version: 11.76.8548
Changes in the system software:
• Bug in the fault logic corrected. With software version NXS00001V172 there was a
possibility with some fault codes that when the fault was activated, the fault code
was shifted in the fault registers so that the last active fault was in the active fault 2
register and the active fault 1 register was empty.
10.3.3. NXP software information
10. 3. 3. 1. NXP00002V156
• Hardware compatible with VB00251G, VB00561F or newer versions.
10. 3. 3. 2. NXP00002V158
• Hardware compatible with VB00251G, VB00561F or newer versions.
• Fixed F25_31 fault from CAN-module.
TABLE 13.
I/O monitoring support to NX option boards.
NXOPT A-series NXOPT B-series NXOPT C-series NXOPT D-series
A1 B1 C2 D3
A2 B2 C3
A3 B4 C4
A4 B5 C5
A5 B9 C6
A8 BE C7
A9 C8
AE CG
AL CI
CJ
CM