EasyManua.ls Logo

Vacon NX - Page 55

Vacon NX
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fault codes and software
24h on-call service phone: +358 (0)40 83 71 150
56
4
FIGURE 15. Fault code F13
Read operation temperature of
the unit from monitoring page.
F13 Undertemperature fault
Did value correspond to
ambient temperature
and temperature lower
than -10 C.
NO
YES
F13 displayed.
Check logged
data in
fault history.
External fault: Temperature is
too low.
Internal fault: Check the
temperature measurment
circuit.
NOTE!
FR9: Power board has its own
temperature measurement, which
can activate F13.

Table of Contents

Other manuals for Vacon NX

Related product manuals