EasyManua.ls Logo

Vacon NX - Page 64

Vacon NX
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fault codes and software
email: service@vacon.com Tel: +358 (0)201 212 575 Fax: +358 (0)204 335 091
65
4
F29 Thermistor fault
F29 displyed.
Checked logged
data in
fault history.
Check
thermistor
connection and
motor
temperature.
Thermistor input on
option board
detected this fault.
External fault. Correct
the thermistor or
cooling of the motor.
NOTE!
Thermistor input has to be
shortcircuited if thermistor
not used.
FIGURE 24. Fault code F29