Fault codes and software
email: service@vacon.com Tel: +358 (0)201 212 575 Fax: +358 (0)204 335 091
89
4
F7
Satu-
ration
Fault
S1 1=Power
2=Power
1
3=Power
2
1=Unit
3=U
phase
4=V
phase
5=W
phase
Signal: ASIC-
DTR. If a caused
defect, the fault
might be on the
power board, in
the power mod-
ule, in the IGBT
or in the internal
cables. Some-
times short cir-
cuit fault
appears simulta-
neously with F7.
- If there is a brake
chopper in use, check
the isolation resistance
and resistance on the
brake resistor.
- FR4-FR8: measure the
power module directly
from its terminals.
Check the capasitors.
TABLE 16.
System software fault codes
Code Sub
code
Module Sub
module
Explanation Fault mode

Table of Contents

Other manuals for Vacon NX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX and is the answer not in the manual?

Vacon NX Specifications

General IconGeneral
Product TypeAC Drive
Control MethodScalar Control
EnclosureIP00, IP21
CommunicationEthernet
SafetySTO (Safe Torque Off)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Ambient Temperature Range-10°C to +50°C (with derating above +40°C)
Cooling MethodAir-cooled, Liquid-cooled

Related product manuals