4. If you enabled the DNP3 protocol, configure the following settings:
Connection type
Interface where DNP3 protocol will be available.
Slave link address
Address of this DGA monitor.
Master link address
Address of the DNP3 master.
Default analog input variation
Data format variation for analog input values. Variations 1 … 6 are available.
5. If you selected Serial port as the connection type, configure the following settings:
Baud rate
Baud rate of the serial connection. Available options are 4800, 9600, 19200, 38400,
57600, and 115200.
Transmission mode
Number of data bits, parity, and number of stop bits used in serial communication.
Available options are 8E1 and 8N2.
6. Set the classes used for the Gas alarm, Gas caution, and Device status events.
7. Select Apply to save your changes.
Select Download to download the DGA monitor device profile in XML format. It is
needed to configure your DNP3 master system.
More information
‣
Connecting to user interface (page 30)
OPT100 User Guide M211858EN-U