3.15 Using protocol test mode
Figure 37 Protocol test mode enabled
1. Connect to the user interface as the Admin user.
2. In the user interface, select Settings > Network > Protocol Test Mode.
3. Check the status of the protocols listed under Protocols. Make sure the protocols you
want are enabled. If they are not, you must enable and configure them first before
continuing this procedure.
4. Select Start to enable the protocol test mode and open the protocol test mode page.
The page is preconfigured with arbitrary default values for measurement
parameters. The values are all dierent to make it easy to verify on the
SCADA side that the correct parameter is being read and displayed. Scroll
the page to reveal all of the fields.
5. To set your own test data:
a. Edit the values as required.
b. Check the checkboxes to enable the desired caution and warning level alerts.
c. Select Update at the bottom of the page to take the new test data into use.
OPT100 User Guide M211858EN-U