6. When instructed to do so, reattach the bleed plug to the bleed valve. Select Continue
when done.
7. When the bleeding sequence is completed, select Continue to exit the tool.
8. Close and lock the door of the DGA monitor cabinet.
Even if the bleeding tool does not complete successfully, you must reattach
the bleed plug in any case before closing the door of the cabinet.
More information
Connecting to user interface (page 30)
5.7
 Installing configuration package
Configuration package file from Vaisala
Installing the configuration package is not possible when the device is measuring.
Installing the configuration package is only needed if requested by Vaisala.
1. If the device is measuring, stop measurement.
2. In the user interface go to Service > Configuration package.