3. Select Bleed > Start to start the bleeding sequence.
The user interface will change to show the bleeding stages and approximate times
between the stages.
4. Follow the progress and instructions on screen. While waiting, open the door of the DGA
monitor cabinet and locate the bleed plug.
5. When instructed to do so, remove the bleed plug from the bleed valve. Select Continue
when done.
Chapter 5 – Troubleshooting
91