Code Alert text Severity Description
2200 Valve 2 failure Error 1. Open the DGA monitor cabinet
and locate valve 2. See Interior
parts (page 22).
2. Check the position of the
manual lock on valve 2. If the
grey knob is pushed down, the
valve is locked and that is
causing the error.
3. Turn the knob counter-
clockwise 90 degrees to open
the lock and resolve the error.
If the lock is open the valve must be
replaced to resolve the error.
Contact Vaisala support.
2201 Lower level sensor failure Error DGA monitor is unable to continue
initialization due to a lower level
sensor failure. The lower level
sensor may be disconnected,
malfunctioning, or broken.
Check if the connections are
functional or if the sensor needs to
be replaced. Contact Vaisala
support.
More information
‣
Generating diagnostics package (page 89)
Chapter 5 – Troubleshooting
87