FAN 1 MINIMUM SPEED FOR HUMIDITY
This function establishes the minimum speed
of Fan 1 when the relative humidity level of
the room exceeds the relative humidity set
point. The speed setting for humidity must be
set higher than the speed setting for
temperature. This value is entered as a
percentage of maximum speed.
The Fan 1 minimum speed is adjusted in 2%
increments from a minimum setting of 12% to
a maximum setting of 100%.
Adjusting the Fan 1 minimum speed for
humidity:
rotate the Selector dial to position (12),
rapidly rotate the Adjuster dial back and
forth to enter secondary function mode,
rotate the Selector dial to position (3),
rotate the Adjuster dial counterclockwise to
decrease the speed, clockwise to increase it.
The Fan 1 minimum speed setting for
humidity is displayed on the ECS.
Example: The relative humidity setting is adjusted to
65%, Fan 1 minimum speed to 25%, and Fan 1
minimum speed for humidity to 50%.
When the humidity level of the room reaches 65% the
minimum speed of Fan 1 gradually increases to
reaches 50% when the humidity level of the room is
75%.
Humidity
CHAPTER 3 - USER’S GUIDE