MINIMUM RAMPING
Minimum ramping is the lowest that the
ramping function can adjust the main set
point to. This is a safety feature.
The minimum ramping setting is adjusted
in 0.5 degree increments from a minimum
setting of -9.5°C (13.5°F) to a maximum
setting of 41.0°C (105.0°F).
Adjusting the minimum ramping setting:
rotate the Selector dial to position (12),
rapidly rotate the Adjuster dial back and
forth to enter secondary function mode,
rotate the Selector dial to position (9),
rotate the Adjuster dial counterclockwise to
decrease the minimum ramping setting,
clockwise to increase it.
The minimum ramping setting is displayed
on the ECS.
Limit
NOTE: When the main set point temperature reaches
the minimum ramping limit, the reduction per day
setting (primary function 9) automatically shuts off.