ECS-3M
SYMPTOM CAUSE and REMEDY
Lo is
continually
displayed
Temperature is below minimum (13.5
°
F or -
10.0
°C).
Probe is disconnected or defective.
Hi is
continually
displayed
Temperature is above maximum (105.0°
F or 41°C).
Probe is short circuited.
Fan(s) or
heater not
operating
Verify whether the fan LED is on. If LED
is on yet fan or heater is not operating,
verify wiring, fan and fuse. Refer Figure
6 for fuse location. If fuse is blown,
replace with fuse of same type.
Stage 3 Fan
or Heater is
operating
erratically
Verify that the software setting switch
located at the rear of the faceplate is
properly set.
Verify the minimum rating (10mA at
230V or 20mA at 230V.
Display is
blank
Verify that the line voltage selector
switch is properly set.
Verify that the 10 pin flat cable between
the main board and the faceplate board
is connected.
F2 displayed
for relative
humidity
Humidity is below minimum (30%).
Probe is disconnected or defective.