INSTALLATION Series
612
38/116
Edition 2018-08-20 605262EE
The «get-command» is: «i:24xx». The answer returns the range «i:24xxytoz». The xx is the value
number, y value is the current lower scale value of buffer and value z the upper scale value.
The format of y and z has following syntax: _ _ _ _ _ _ _ _._ _ _ _ _
Examples: i:2400-0012345.12345to00123456.12345
i:2401-0001000.00000to00001000.00000
i:240200001000.00000to00001500.00000
Example «get-command» with Terminal: Get the range of Pressure Sensor 1:
The «range of pressure and position values» is independent of the data type, equal for «signed integer»
and «floating point».
The internal accuracy of valve is for all positions 100’000 steps and for all pressures
1’000’000 steps. If the range of pressure and position values is rising, the accuracy of
pressure and position will not rise. There is
only the gain factor between the VAT valve
and the EtherCAT Master which will be adapted.
(upper scale value - lower scale value) 1
If at startup the scale values in the memory are out of range or the rule above is
broken the default values are taken. In this case the get command i:24 add a string
“False”:
Example: s:24031234.56to7890 set the range of position from 1234.56 (= closed position) to 7890 (=
opened position)
Example: s:24000to100.75 set the range of pressure from 0 (= 0 V) to 100.75 (= 10 V)
Example: s:2407-10.5to20.5 set the range of Position setpoint from -10.5 (=closed position)
to 20.5 (=opened position)