Determining Mag Probe Length Determining Mag Probe Length for Media-Isolated Installations
18
3. Measure from the top of the riser to the bottom of the tank and record this distance as “D2”.
4. Subtract “D1” from “D2”, then add 7 inches, to determine the correct probe length.
Figure 10. Determining Mag Probe Length for Installation in a Vapor Extractor Riser
Determining Mag Probe Length for Media-Isolated Installations
If tank’s inside diameter is unknown, perform the following procedure (ref. Figure 11):
1. Measure the distance from the inside bottom of the tank to the inside top of the tank (A).
2. Order a probe length of B (where B = A + 6”).
Figure 11. Calculating the Correct Mag Probe Length for Media-Isolated installation
Bushing
Tank
AB
6"
Pump
probes\mediaiso.eps
A + 6" = Probe length (B)