EasyManuals Logo

Veeder-Root TLS User Manual

Veeder-Root TLS
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
TLS Magnetostrictive Probes International Installation Guide Probe Riser Pipe Installation
17
Probe Riser Pipe Installation
A riser assembly consisting of a riser (either 2- or 3-inch [50.8 or 76mm] nominal bore galvanised steel pipe
threaded 2- or 3-inch BSPT at each end) and a 2- or 3-inch riser cap, designed specifically for the efficient
installation of Veeder-Root magnetostrictive probes, should be used for Mag Probe installation (see
Figure 16).
Riser caps are normally fitted at the time of probe installation by Veeder-Root authorised engineers. An optional
cable shield is available for 3-inch (76mm) riser caps, if required.
Non–standard or locally supplied risers may be made from 2- or 3-inch nominal bore galvanised steel pipe
threaded 2- or 3-inch at each end (see
Table 2 for allowable riser dimensions).
Remove the plug from the tank socket. Install a 2-inch (50mm nominal bore) or 3-inch (80mm nominal bore) riser
using an appropriate thread-sealing compound. Reducers are available for 4-inch (102mm nominal bore) sockets.
If the probes are not to be installed immediately, cap the riser.
Where locally supplied, 2-inch risers should be seamless, have a 2-inch ID, and be free of burrs.
Figure 16. Veeder-Root Riser Cap Assemblies
DN = Diameter Nominal, NPS = Nominal pipe size, Pipe type is iron or schedule 40 steel
*Maximum allowable inside diameter for Mag Probe installation.
Table 2. Dimensions for Steel Riser Pipes and Mag Probe Floats
DN Nom Pipe
(mm)
NPS Nom Pipe
(inch)
ID Nom Pipe
(mm)
ID Nom Pipe
(inch)
OD Max Float
(mm)
OD Max Float
(inch)
OD Min Float
(mm)
ID Max* Pipe
(mm)
25 1 26.65 1.049 29.34 1.155 29.08 N/A
50 2 52.51 2.067 47.63 1.875 46.86 55
80 3 77.93 3.068 76.58 3.015 75.82 85
100 4 102.26 4.026 95.63 3.765 94.87 110
Hummel probe leader
cable gland
Hummel probe leader
cable gland
51mm Threaded Riser Cap Assembly
Shield (if required)
Use fitting tool 705-100-3033
to install or remove the cap
3-inch (76mm) BSP riser cap
76mm BSPT Riser Cap Assembly
50.8mm (2”)
galvanised steel
riser cap
031-3

Table of Contents