89
11 Supplement
VEGAPULS 63 • Modbus and Levelmaster protocol
41364-EN-170711
Response:
Parameter Length Code/Data
Set Receive to Transmit Delay 6 characters ASCII UuuROK
Report Number of Floats
Request:
Parameter Length Code/Data
Set Receive to Transmit Delay 4 characters ASCII UuuF
Response:
Parameter Length Code/Data
Set Receive to Transmit
Delay
5 characters ASCII UuuFn
n = number of measurement values (0, 1 or 2)
Report Receive to Transmit Delay
Request:
Parameter Length Code/Data
Report Receive to Transmit Delay 4 characters ASCII UuuR
Response:
Parameter Length Code/Data
Report Receive to Trans-
mit Delay
7 characters ASCII UuuRmmm
mmm = milliseconds (50 up to 250), default = 127 ms
Error codes
Error Code Name
EE-Error Error While Storing Data in EEPROM
FR-Error Erorr in Frame (too short, too long, wrong data)
LV-Error Value out of limits