94
11 Supplement
VEGAPULS 63 • Modbus and Levelmaster protocol
41364-EN-170711
ScadaPack
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
3
2
13
45
5
2
1
3
4
9
6
7
8
2off
on
( )
(
)
(-)
(-)
+8 +30
Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 54: Connection of VEGAPULS 63 to RTU ScadaPack
1 VEGAPULS 63
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter Value
Baud Rate 9600
Floating Point Format Code 0
RTU Data Type Floating Point
Input Register Base Number 30001
The basic number of the input registers is always added to the input register address of VEGAPULS
63.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.
11.7 Dimensions
The following dimensional drawings represent only an extract of all possible versions. Detailed
dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".