UPS Power
(kVA)
PF
Input
voltage (V)
Output
Voltage (V)
Battery
Number (+
and -)
Charge
current
(Max) (A)
Input
Current (A)
Output
Current (A)
Max Battery Discharge
current with 32 blocks per
string (A)
(3-In 3-Out)
15
(3-In 1-Out)
1,0 230 230 16 12 31 66 46
15
(3-In 3-Out)
1,0 240 240 16 12 30 21 46
15
(3-In 1-Out)
1,0 240 240 16 12 30 63 46
20
(3-In 3-Out)
1,0 220 220 16 12 41 30 62
20
(3-In 1-Out)
1,0 220 220 16 12 41 91 62
20
(3-In 3-Out)
1,0 230 230 16 12 39 29 62
20
(3-In 1-Out)
1,0 230 230 16 12 39 87 62
20
(3-In 3-Out)
1,0 240 240 16 12 37 28 62
20
(3-In 1-Out)
1,0 240 240 16 12 37 84 62
30
(3-In 3-Out)
1,0 220 220 16 16 59 45 93
30
(3-In 3-Out)
1,0 230 230 16 16 57 43 93
30
(3-In 3-Out)
1,0 240 240 16 16 54 42 93
40
(3-In 3-Out)
1,0 220 220 16 16 75 61 124
40
(3-In 3-Out)
1,0 230 230 16 16 72 58 124
40
(3-In 3-Out)
1,0 240 240 16 16 69 56 124
Table 2.2 Maximum Current Values (continued)
14 Proprietary and Confidential ©2024 Vertiv Group Corp. 2 Installation and Operation
Vertiv™ Liebert® MTP Online UPS User Manual 20-40-80kVA