Vertiv
™
| Liebert® EXL
™
S1 Touchscreen Control User Manual | 72
Rectifier
Alar
m
Overtemperature Phase V-B
22-
062
Set when Phase V temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
Overtemperature Phase W-C
22-
063
Set when Phase W temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
Overtemperature B Phase U-A
22-
073
Set when Phase U temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
Overtemperature B Phase V-B
22-
074
Set when Phase V temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
Overtemperature B Phase W-C
22-
075
Set when Phase W temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
DC Overvoltage 22-102
Set when the rectifier detects DC bus voltage
above threshold P1753.29.
Table 10 All Liebert® EXL™ S1 Alarms (continued)
Component Type Text Display ID Description