Vertiv
| Liebert® EXL
S1 Touchscreen Control User Manual | 72
Rectifier
Alar
m
Overtemperature Phase V-B
22-
062
Set when Phase V temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
Overtemperature Phase W-C
22-
063
Set when Phase W temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
Overtemperature B Phase U-A
22-
073
Set when Phase U temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
Overtemperature B Phase V-B
22-
074
Set when Phase V temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
Overtemperature B Phase W-C
22-
075
Set when Phase W temperature is greater then P
1151 setting (Def = 80°C).
Rectifier
Alar
m
DC Overvoltage 22-102
Set when the rectifier detects DC bus voltage
above threshold P1753.29.
Table 10 All Liebert® EXL™ S1 Alarms (continued)
Component Type Text Display ID Description

Table of Contents

Other manuals for Vertiv Liebert EXL S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert EXL S1 and is the answer not in the manual?

Vertiv Liebert EXL S1 Specifications

General IconGeneral
BrandVertiv
ModelLiebert EXL S1
CategoryUPS
LanguageEnglish

Related product manuals