Table 11 All EXL S1 Faults
Component
Typ
e
Text Display ID Description
Battery
Faul
t
Battery Test Failure
34-
023
Battery
Faul
t
Battery Overcurrent Fault
34-
070
BCB Control algorithm has detected an overcurrent
condition. BCB Open command issued.
Battery
Faul
t
Battery Ground Fault 34-071
Enabled by Input Function 22 BCB GND Fault. Battery
ground fault detector is tripped.
Bypass
Faul
t
E.P.O. 31-020
Bypass
Faul
t
Bypass hardware failure 31-021
Output voltage is out of tolerance and the bypass
input is within tolerance (SW detected fault
monitoring output signals).
Bypass
Faul
t
Bypass hardware failure 31-022
Set when the bypass static switch board is not
installed (i.e., bypass voltage < 170 V).
Bypass
Faul
t
Backfeed protection 31-023 Back feed fault has been detected. Enabled by P142.
Bypass
Faul
t
Overload 31-026
Bypass
Faul
t
Bypass Failure During Line
Support
31-027
Bypass
Faul
t
Parallel Failure During Support 31-028
Bypass
Faul
t
Overtemperature 31-036 Bypass heat sink overtemperature.
Bypass
Faul
t
Back feed power supply failure 31-102
Charger/Boos
ter
Faul
t
Charger Temperature high 33-018
Set when temperature is greater then P 1152 value
(see Overload specification)
Charger/Boos
ter
Faul
t
Temperature Probe Broken 33-019
Buck booster temperature sensor fault SW detected;
based on M.I. value outside sensor limit interval -15°C
< T< +150°C for 60 seconds (P 1780.6).
Charger/Boos
ter
Faul
t
Charger Temperature high
33-
020
Booster/Charger filter overtemperature. (M.I. XP31
pin 1-6).
Charger/Boos
ter
Faul
t
Charger Desaturation 33-021 Charger desaturation.
Charger/Boos
ter
Faul
t
Charger Redundant Voltage
error
33-
022
If the absolute value of the difference between
primary and secondary battery voltage acquisition is
greater than a predefined threshold, a fault is issued
and the Booster/charger is turned Off because the
voltage measurement is corrupted.
Charger/Boos
ter
Faul
t
Charger DC Bus
33-
023
Set when DC voltage +/- is greater than the P753.i15
threshold.
Charger/Boos
ter
Faul
t
E.P.O.
33-
035
Charger/Boos
ter
Faul
t
Charger Voltage Out of Limit
33-
025
The charger is switched Off due to an overvoltage on
the battery. The time until switch Off depends on the
overvoltage value.
Charger/Boos
ter
Faul
t
Buck-Booster Overcurrent
33-
058
The current limitation control has tripped the
booster.

Table of Contents

Other manuals for Vertiv Liebert EXL S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert EXL S1 and is the answer not in the manual?

Vertiv Liebert EXL S1 Specifications

General IconGeneral
BrandVertiv
ModelLiebert EXL S1
CategoryUPS
LanguageEnglish

Related product manuals