504402079908 S600E
PART CODE - 504402079908 USER MANUAL-S600E 5
d with fuse having the same electric parameters by qualified
personnel.
The
area
housing
the
communication
board
contains
static
sensitive
components,
therefore
it
is
necessary
to
adopt
all
the
appropriate ESD-proof measures before accessing this area.
In
order
to
satisfy
the
conditional
short
circuit
current
rating,
Icc
at
10kA
symmetrical
rms,
the
specified
upstream
breakers
must comply with an IEC 60947 series standard.
The
UPS
is
unable
to
automatically
isolate
the
neutra
l
connection,
ensure
to
have
4P
breaker
upstream
and
downstream
the
UPS in case of IT distribution.
Like
other
types
of
large
power
equipment,
the
UPS
and
battery
circuit
breaker
box/battery
cabinet
contain
high
voltages.
This equipment meets the IP20 standard, and other safety panels are fitted inside the equipment.
The UPS may be operated in complete safety, provided the general instructions and the steps recommended in this manual
are followed.
This UPS system receives power from more than one source. All DC and AC power sources must be disconnected before
servicing.
This UPS includes several circuits that are energized by high AC as well as DC voltages. Check for voltage with both AC and
DC voltmeters before working inside the UPS.
All equipment maintenance and servicing procedures involving internal access require the use of a tool and should be carried
out by trained personnel only. There are no user-serviceable parts behind the covers that require a /key for removal.
All battery maintenance and servicing procedures require the use of tools and should be carried out by trained personnel only.
Take special care when working with the batteries associated with this UPS. When connected together, the battery terminal
voltage will exceed 320Vdc and is potentially lethal.
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a
large bank of battery cells. These precautions should be followed scrupulously at all times. Special attention should be paid to
the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-
fighting facilities.
General safety precautions (For users)
Multiple power inputs (For users)
User serviceable components (For service personnel)
Battery voltage: 320Vdc - 540Vdc (For service personnel)