USER MANUAL-S600E
96
S600E
Appendix 1 LCD Parameter Settings
System
Auto restart delay
0
~
999 seconds
10; Single unit only
Remote power on delay
0
~
999 seconds
0
Remote shut-down delay
0
~
999 seconds
0
Dry contact
1
(Output)
UPS fault
Low battery
Dry contact 2 (Output)
Low battery, On bypass, On battery,
UPS fault
UPS fault
Dry contact 3 (Input)
shut-down, Maintain mode
Maintain mode
Dry contact 4 (Input)
shut-down, Maintain mode
Maintain mode
Output
Frequency selection
Auto, BypEna; Auto, BypDisa;
50Hz, BypDisa; 60Hz, BypDisa
Auto, BypEna
Inverter sync range
±0.5Hz, ±1.0Hz, ±2.0Hz, ±3.0Hz,
±4.0Hz, ±5.0Hz
±3.0Hz
Bypass voltage upper limit
Bypass voltage lower limit
only
when
the 'Run
mode' is
set to
'ECO
mode'
ECO requalification time
5, 15, 30 (min)
30
Parallel
Frequency selection
Auto, BypEna; Auto, BypDisa;
50Hz, BypDisa; 60Hz, BypDisa
Auto, BypEna
System parallel No.
1~4
1
Battery
Local/Parallel battery total Ah
7
~
3000Ah
External battery cabinet count
Auto test, 0
~
10
Auto test
Low battery time
2
~
30 (min)
2
Battery test interval
Disable, 8 weeks, 12 weeks,
weeks
,
20 weeks
,
26 weeks
Disable