USER MANUAL-S600E
96
S600E
Appendix 1 LCD Parameter Settings
Menu
Item
Setting range
Default setting
System
Auto restart
Disable, Enable
Enable
Auto restart delay
0
999 seconds
10; Single unit only
Guaranteed shut
-
down
Disable, Enable
Disable
Remote control
Disable, E
nable
Enable
Remote power on delay
0
999 seconds
0
Remote shut-down delay
0
999 seconds
0
Redundant
NO, YES
YES
LBS select
Disable, Master, Slave
Disable
IT system compatibility
Disable, Enable
Disable
Dry contact
1
(Output)
Low battery, On byp
ass, On battery,
UPS fault
Low battery
Dry contact 2 (Output)
Low battery, On bypass, On battery,
UPS fault
UPS fault
Dry contact 3 (Input)
Battery mode shut
-
down, Any mode
shut-down, Maintain mode
Maintain mode
Dry contact 4 (Input)
Battery mode shu
t
-
down, Any mode
shut-down, Maintain mode
Maintain mode
Output
Voltage selection
220V, 230V, 240V
220V
Start
-
up on bypass
Disable, Enable
Disable
Frequency selection
Auto, BypEna; Auto, BypDisa;
50Hz, BypDisa; 60Hz, BypDisa
Auto, BypEna
Inverter sync range
±0.5Hz, ±1.0Hz, ±2.0Hz, ±3.0Hz,
±4.0Hz, ±5.0Hz
±3.0Hz
Bypass voltage upper limit
+10%, +15%, +20%
+20%
Bypass voltage lower limit
-
10%,
-
20%,
-
30%,
-
40%
-
40%
Bypass frequency range
±5Hz, ±10Hz
±10Hz
Run mode
Normal, ECO mode
Normal
ECO
voltage range
±5%, ±10%, ±15%
±10%
Appear
only
when
the 'Run
mode' is
set to
'ECO
mode'
ECO frequency range
±1Hz, ±2Hz, ±3Hz
±3Hz
ECO requalification time
5, 15, 30 (min)
30
Output phase No.
1 phase, 3 phases
3 phases
Parallel
Vol
tage selection
220V, 230V, 240V
220V
Frequency selection
Auto, BypEna; Auto, BypDisa;
50Hz, BypDisa; 60Hz, BypDisa
Auto, BypEna
Run mode
Normal, ECO mode
Normal
Redundant
NO, YES
YES
System parallel No.
14
1
Output phase No.
1 phase, 3
phases
3
phases
Sync parallel parameters
Button
Button
Battery
Shared battery
Enable, Disable
Disable
Local/Parallel battery total Ah
7
3000Ah
External battery cabinet count
Auto test, 0
10
Auto test
Low battery time
2
30 (min)
2
Battery replaced tim
e
YYYY
-
MM
-
DD HH:MM:SS
2000
-
01
-
01 0:00:00
Battery test interval
Disable, 8 weeks, 12 weeks,
16
weeks
20 weeks
26 weeks
Disable