USER MANUAL-S600E
60
S600E
After EPO, if the mains input is present, the UPS control circuit will remain active; however, the output is interrupted.
To completely remove all mains power from the UPS, first disconnect the UPS external mains switches, and then
disconnect the battery terminals.
5.6
Automatic Restart
In the event of a mains power failure, the UPS draws power from the battery in order to supply the load until the
batteries are discharged, at which point the UPS will shut down.
The UPS will restart automatically and resume supplying power to the load:
Once the mains power supply is restored.
If the UPS Auto Restart function is enabled.
After the Auto Restart delay has expired (default: 10s). During the Auto Restart delay, the UPS will charge the
battery in order to provide a safety margin for equipment shut-down if input power fails again.
If the Auto Restart function is disabled, you can restart the UPS manually by pressing the power button.
5.7
Language Selection
The LCD menus are available in two languages: Chinese, English.
Language selection procedure:
1.
Access the main menu screen and press the
or
key to switch the cursor to select 'Settings', then press
the
key to confirm. See Figure 5-14.
Figure 5-14 Main menu
2.
Press the
key to move the cursor to 'Monitor', see Figure 5-15.
Figure 5-15 Monitor interface
3.
Press the
key to highlight the language, see Figure 5-16.