EasyManua.ls Logo

Vertiv Liebert S600E - Electrical Specifications (Inverter Output); Electrical Specifications (Bypass Input)

Vertiv Liebert S600E
101 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
USER MANUAL-S600E
95
S600E
10.6
Electrical Specifications (Inverter Output)
Table 10-6 Inverter output (to critical load)
Item Unit
Rat
ed power (kVA)
10kVA
-
20kVA
Rated AC voltage
1
Vac
380/400/415
(3
-
phase
4
-
wire,
with
neutral
reference
to
the
bypass
neutral)
(3-in 3-out)
Frequency
2
Hz
50/60
Overload
%
For
linear load requirements:
< 105%, continuous;
105 - 125% of rated load, 5min;
125 - 150% of rated load, 1min;
> 150%, 200ms
Non
-
linear load capacity
3
%
100%
Steady state voltage stability
%
±1% for balanced three phase load;
±2% for unbalanced load
Transient voltage response
4
%
±5% for 100% rated linear load step
Total harmonic voltage
%
2% (100% linear load);
5% (100% non-linear load)
Synchronisation window
Hz
Rated frequency ±0.5, ±1, ±2, ±3 (settable)
Slew
rate
(max.
change
rate
of
synchronisation
frequency)
Hz/s
Setting range: 0.2, 0.5, 1 (UPS module), 0.2 (parallel system)
1.
Factory set to 380V. 400V or 415V can be selected by service engineer at site.
2.
Factory set to 50Hz. 60Hz can be selected by service engineer at site. Note that the system frequency may only be changed
when the UPS is in bypass mode. It is strictly prohibited to change the system frequency when the UPS supplying the load via
the inverter.
3.
EN 50091-3 (1.4.58) crest factor 3:1, non-linear load.
4.
IEC/EN 62040-3/EN 50091-3 also for 0 - 100% - 0 load transient. Transient recovery time: returns to within 5% of steady state
output voltage within half a cycle.
10.7
Electrical Specifications (Bypass Input)
Table 10-7 Bypass input
Item Unit
Rated power (kVA)
10kVA-20kVA
Rated AC voltage
1
Vac
380/400/415
,
3
-
phase
4
-
wire,
sharing
neutral
with
the
rectifier
input
and
providing
neutral reference for the output, (3-in 3-out)
Overload
%
Based on nominal voltage and rated load current under apparent power:
< 105%, continues;
105 - 125% of rated load, 10min;
125 - 150% of rated load, 1min;
> 150%, 200ms
Frequency
2
Hz
50/60
Bypass voltage tolerance
%Vac
Upper limit: +10%, +15% or +20%, default: +20%;
Lower limit: -10%, -20%, -30% or -40%, default: -40%
Bypass frequency
tolerance
%
±5% or ±10%, default: ±10%
Synchronisation window
Hz
Rated frequency ±0.5, ±1, ±2, ±3, ±4,
±5 (settable); ±5 by default
1.
Factory set to 380V. 400V or 415V can be selected by service engineer at site.
2.
Factory set to 50Hz. 60Hz can be selected by service engineer at site.

Table of Contents

Related product manuals