Figure 6.47 Options setup, page 2 of 2
Low Pressure Alarm Delay—Sets how long a Low Pressure alarm will be delayed when any compressor
starts. This is also known as the Winter Start Delay Timer.
Compressor Sequence ON TD—Sets the time delay between each compressor’s activation during startup.
Compressor All ON TD—Sets the time delay for all compressors to continue to run once all four
compressors have started during the startup sequence.
Comp Next Start Delay—Sets the time delay between each compressor’s activation during normal
operation.
Lead Tandem—Sets the lead tandem compressor bank when the unit is activated. Can be set for Tandem
1 or Tandem 2.
Vertiv | Liebert® XDC™ User Manual | 108