Models - 60 Hz XDC160 Glycol Floor Stand - 60Hz - 40% PG
Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)
Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43)
Performance Data
Cooling capacity, tons (kW) 42.5 (149.4)
Total Heat Rejection, kW 192.6
Flow, GPM 206
Pressure Drop, psi (ft water) 37.2 (85.9)
Heat Rejection Equipment
Drycooler DNT 940A 2 x DNT 880A*
Drycooler Pressure Drop, psi (ft water) 6.7 (15.5) 2.9 (6.6)
Glycol pump package - 10hp 9A31258G3
Pump Control Package - 208V 9A34606G47
Pump Control Package - 460V 9A32114G4
Pump Total Head @ 204 GPM, ft water 145
Water regulating valve size 1-1/4"
Piping Connections
Water / glycol supply and return lines 2-5/8"
*When multiple drycoolers are used ensure flow is balanced.
Table 11.3
Floor stand specifications—Liebert XDC with 40% propylene glycol
Models - 60 Hz XDC160 Glycol Floor Stand - 60Hz - 40% EG
Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)
Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43)
Performance Data
Cooling capacity, tons (kW) 42.5 (149.4)
Total Heat Rejection, (kW) 192.6
Flow, GPM 204
Pressure Drop, psi (ft water) 35.9 (82.9)
Heat Rejection Equipment
Drycooler DNT 940A 2 x DNT 880A*
Drycooler Pressure Drop, psi (ft water) 6.5 (15.1) 2.7 (6.3)
Table 11.4
Floor stand specifications—Liebert XDC with 40% ethylene glycol
Vertiv | Lieber XDC™ User Manual | 129