EasyManuals Logo

Vertiv Liebert XDC User Manual

Vertiv Liebert XDC
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
Models - 60 Hz XDC160 Glycol Floor Stand - 60Hz - 40% EG
Glycol pump package - 10HP 9A31258G3
Pump Control Package - 208V 9A34606G47
Pump Control Package - 460V 9A32114G4
Pump Total Head @ 204 GPM, ft water 145
Water regulating valve size 1-1/4"
Piping Connections
Water / glycol supply and return lines 2-5/8"
*When multiple drycoolers are used ensure flow is balanced.
Table 11.4 Floor stand specifications—Liebert XDC with 40% ethylene glycol (continued)
Vertiv | Lieber XDC™ User Manual | 130

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert XDC and is the answer not in the manual?

Vertiv Liebert XDC Specifications

General IconGeneral
BrandVertiv
ModelLiebert XDC
CategoryFreezer
LanguageEnglish

Related product manuals