LaserPLUS Product Guide VESDA
®
12
Default Settings
Parameter Default Value
Range
Access
Level
Minimum Maximum
Event Log - Events
• Smoke Level Enabled N/A N/A Adm
• Alarms Enabled N/A N/A Adm
• Faults Enabled N/A N/A Adm
• User Action Enabled N/A N/A Adm
Fire 2 Threshold 2% obs/m 0.625%
obs/ft.
0.02% obs/m
0.0062% obs/ft.
20.% obs/m
6.25% obs/ft.
Adm
Fire 1 Threshold 0.2% obs/m
0.0625% obs/ft.
0.015% obs/m
0.0046% obs/ft.
2% obs/m
0.6250% obs/ft.
Adm
Action Threshold 0.14% obs/m
0.044% obs/ft.
0.010% obs/m
0.0031 obs/ft.
1.995% obs/m
(0.6234% obs/ft.
Adm
Alert Threshold 0.08% obs/m
0.025% obs/ft.
0.005% obs/m
0.0015% obs/ft.
1.990% obs/m
0.6218% obs/ft.
Adm
Alarm Delays…Fire 2 10 seconds 0 seconds 60 seconds Adm
Alarm Delays…Fire 1 10 seconds 0 seconds 60 seconds Adm
Alarm Delays…Action 10 seconds 0 seconds 60 seconds Adm
Alarm Delays…Alert 10 seconds 0 seconds 60 seconds Adm
Delay Times Simultaneous Simultaneous Cumulative Adm
Instant Fire Disabled Enabled Disabled Adm
Change-over Times:
•Day
• Night
07:00:00
19:00:00
Two seconds 11:59:58 Adm
Weekend Saturday & Sunday Adjust to suit
environment
Adjust to suit
environment
Adm
Holidays:
• First Day
•Last Day
1-Jan-90
1-Jan-90
Adjust to suit
environment
Adjust to suit
environment
Adm
Smoke Change:
•Change By
• Min. Interval
0.02% obs/m
0.0062% obs/ft.
2 seconds
0.005% obs/m
0.0015% obs/ft.
2 seconds
0.2% obs/m
0.0625% obs/ft.
10 seconds
Adm
Dst
AutoLearn 14 days
0 Hours
0 Minutes
0 Days
0 Hours
15 minutes
15 days
23 Hours
59 Minutes
Adm
Adm
Adm