Codes and Standards Information for Air Sampling Smoke Detection
ONORM F3014
ONORM F3014, transport times for all tubes (including capillaries) must not exceed 60 seconds from any hole. This means that the pre-
designed pipe networks that include capillaries cannot be used.
AS1603.8
The performance of this product is dependent upon the configuration of the pipe network. Any extensions or modifications to the pipe
network may cause the product to stop working correctly. You must check that ASPIRE2 approves alterations before making any changes.
ASPIRE2 is available from your VESDA ASD distributor.
AS1603.13
AS1603.13: VESDA detectors are not compliant with the pressure testing in this standard.
FM Approved Applications
The product must be powered from VPS-100US-120, VPS-100US-220 or VPS-220 only.
European Installations
The product must use a power supply conforming to EN54: Part 4.
Document: 10278_03
The product complies with the following standards.
AS1603.8-1996
GEI 1-048:Jan 1997
FM3230-3250 FM3820
21 CFR 1010.221 CFR 1010.3
AS2211 EN60950 AS/NZS3548 FCC Class B
EN 50081-1 EN 50130-4
UL 268 UL268A
UL and FM Compliancy
All installers must ensure that environments that require UL approved product must have the requirements of a remote display or FACP
connected to the detectors. Failure to do so will void product compliance for UL and FM certification that is stated on the detector approval
and rating label.
Approval Certification:
Vision Fire & Security have had this product tested and approved by UL and FM. This product is fully listed and compliant as long as the
exception in UL268 is adhered to. Please see section 17.5 of UL268, 2003 Edition.
“17.5 A lamp or equivalent means shall be provided on a spot-type detector head or base to identify it as the unit from which the alarm was
initiated”.
Exception: The alarm-indicating-means is not required on a detector whose use is restricted to a specific control unit that identifies
the individual detector in alarm.
As long as these models are connected to a remote display or to a Fire Alarm Control Panel (FACP) that identifies if the detector is in alarm
then it is a compliant product.