Name Data type Address
(Instance
DB)
Default
value
Comment
LADDR WORD 0.0 300h This parameter is not evaluated. Always
the internal I/O periphery is addressed.
CHANNEL INT 2.0 0 Channel number
SW_GATE BOOL 4.0 FALSE Enables the Software gate
CTRL_DO BOOL 4.1 FALSE Enables the output
False: Standard Digital Output
SET_DO BOOL 4.2 FALSE Parameter is not evaluated
JOB_REQ BOOL 4.3 FALSE Initiates the job (edge 0-1)
JOB_ID WORD 6.0 0 Job ID
JOB_VAL DINT 8.0 0 Value for write jobs
STS_GATE BOOL 12.0 FALSE Status of the internal gate
STS_STRT BOOL 12.1 FALSE Status of the hardware gate
STS_LTCH BOOL 12.2 FALSE Status of the latch input
STS_DO BOOL 12.3 FALSE Status of the output
STS_C_DN BOOL 12.4 FALSE Status of the down-count
Always indicates the last direction of
count. After the first SFB call STS_C_DN
is set FALSE.
STS_C_UP BOOL 12.5 FALSE Status of the up-count
Always indicates the last direction of
count. After the first SFB call STS_C_UP
is set TRUE.
COUNTVAL DINT 14.0 0 Actual count value
LATCHVAL DINT 18.0 0 Actual latch value
JOB_DONE BOOL 22.0 TRUE New job can be started
JOB_ERR BOOL 22.1 FALSE Job error
JOB_STAT WORD 24.0 0 Job error ID
Parameters
VIPA System 300SDeployment I/O periphery
Counter > SFB 47 - COUNT - Counter controlling
HB140 | CPU-SC | 312-5BE13 | GB | 15-50 104