5.3.4 Digital Input Address Maps
5.3.4.1 Digital Input / DI State Type Address Map
Digital Input / DI State Type Address Map
Last Reset Date 32-Bit Integer Read Unix Time
Total Time 32-Bit Integer Read Seconds
Cycle Time 32-Bit Integer Read Seconds
34 Interlock State Boolean Read
0 = Inactive
1 = Active Interlock
35 Alarm Bitfield 16-Bit Bitfield Read
See 5.5.4 Digital Input Alarm Bitfield
When accessed as a Coil,