74
5.5.3 Sensor Input Alarm Bitfield
Sensor Input Alarm Bitfield
The sensor reading drops below the Low Alarm setpoint.
The sensor reading rises above the High Alarm setpoint.
The sensor reading drops below the Low Low Alarm setpoint.
The sensor reading rises above the High High Alarm setpoint.
5 Electrode in service longer than alarm time setpoint.
Input Failure † 7
The sensor reading is invalid (out of range, sensor fault,
wiring incorrect, sample error, or I/O card failure). This alarm
will stop the control for any output using the sensor.
All sensor types
8 The sensor requires calibration. All sensor types
† Compatibility Note: In controller software versions 3.09 and earlier, Bit 5 was used for “Out of Range”
errors and Bit 6 was used for “Sensor Fault” alarms. In software versions 3.11 and later, these alarms
are combined with other types of sensor “Input Failures” reported using Bit 7.
5.5.4 Digital Input Alarm Bitfield
Digital Input Alarm Bitfield
The input is in the state selected to generate an alarm.
Total 2 The meter total exceeds the limit.
Total Range 3 The range of the totalizer is exceeded.
This digital input circuit is no longer functioning.
Flow Verify 5 Feed Monitor unable to verify chemical feed.
Low 6 Flowrate below the Low Alarm setpoint.
High 7 Flowrate above the High Alarm setpoint.