5.3.7.3 Pulse Relay Output / Flow Proportional Control Mode Address Map
Pulse Relay Output / Flow Proportional Control Mode Address Map
Address
Name
Data Encoding
Permissions
Value
0
Time On 32-Bit Integer Read Seconds
1
2
Total Time 32-Bit Integer Read Seconds
3
4
Output 32-Bit Float Read Percent
5
6
Target PPM 32-Bit Float Read/Write 1 – 1,000,000 ppm
7
8
9
10
11
12
13
14
15
16
Specific Gravity
Of Product
32-Bit Float Read/Write 0 – 9.999 mg/l
17
18
Pump Capacity 32-Bit Float Read/Write
0 – 10,000 Volume Units
Hour
19
20
Pump Setting 32-Bit Float Read/Write 0 – 100%
21
22
Output Time Limit 32-Bit Integer Read/Write 0 – 86,399 Seconds
23
24
Low Cycles Limit 32-Bit Float Read/Write 0.00 – 100.00
25
26
Hand Output 32-Bit Float Read/Write 0 – 100%
27
28
Hand Time Limit 32-Bit Integer Read/Write 0 – 86,399 Seconds
29
30
Reset Output Timeout
Boolean
Read/Write
Write 1 to Reset Output Timeout
31
32
Reset Time Total
Boolean
Read/Write
Write 1 to Reset Time Total
33 HOA Setting 16-Bit Integer Read/Write
0 = Hand, 1 = Off,
2 = Auto Mode
34
Status
16-Bit Status
Read
See 5.4 Status Register Codes
35 Alarm Bitfield 16-Bit Bitfield Read
See 5.5.6 Relay Output Alarm Bitfield
When accessed as a Coil,
Returns 1 if any alarm is active