ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 103 of 140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon SNVT
Lon Direction
Modbus
Address
15
Fire Rate In
SMD_BAS_IP_HTR_15_[9]
AV:1709
Data Float
335
nvoHTR_15_10
inc count (9)
Output (non-polled)
31709
15
Fire Rate Out
SMD_BAS_IP_HTR_15_[10]
AV:1710
Data Float
336
nvoHTR_15_11
inc count (9)
Output (non-polled)
31710
15
Unit Type
SMD_BAS_IP_HTR_15_[11]
AV:1711
Data Float
337
nvoHTR_15_12
inc count (9)
Output (non-polled)
31711
15
Unit Size
SMD_BAS_IP_HTR_15_[12]
AV:1712
Data Float
338
nvoHTR_15_13
inc count (9)
Output (non-polled)
31712
15
Value State
SMD_BAS_IP_HTR_15_[13]
AV:1713
Data Float
339
nvoHTR_15_14
inc count (9)
Output (non-polled)
31713
15
Net Remote Setpt
SMD_BAS_IP_HTR_15_[14]
AV:1714
Data Float
340
nvoHTR_15_15
inc count (9)
Output (non-polled)
31714
15
Run Cycles Upper
SMD_BAS_IP_HTR_15_[15]
AV:1715
Data Float
341
nvoHTR_15_16
inc count (9)
Output (non-polled)
31715
15
Run Cycles Lower
SMD_BAS_IP_HTR_15_[16]
AV:1716
Data Float
342
nvoHTR_15_17
inc count (9)
Output (non-polled)
31716
15
Run Hours Upper
SMD_BAS_IP_HTR_15_[17]
AV:1717
Data Float
343
nvoHTR_15_18
inc count (9)
Output (non-polled)
31717
15
Run Hours Lower
SMD_BAS_IP_HTR_15_[18]
AV:1718
Data Float
344
nvoHTR_15_19
inc count (9)
Output (non-polled)
31718
15
Oxygen Level
SMD_BAS_IP_HTR_15_[19]
AV:1719
Data Float
345
nvoHTR_15_20
inc count (9)
Output (non-polled)
31719
Blr Addr 16
16
Comm Address
SMD_BAS_IP_HTR_16_[0]
AV:1800
Data Float
346
nvoHTR_16_1
inc count (9)
Output (non-polled)
31800
16
Unit Status
SMD_BAS_IP_HTR_16_[1]
AV:1801
Data Float
347
nvoHTR_16_2
inc count (9)
Output (non-polled)
31801
16
Fault Code
SMD_BAS_IP_HTR_16_[2]
AV:1802
Data Float
348
nvoHTR_16_3
inc count (9)
Output (non-polled)
31802
16
Outlet Temp
SMD_BAS_IP_HTR_16_[3]
AV:1803
Data Float
349
nvoHTR_16_4
inc count (9)
Output (non-polled)
31803
16
FFWD Temp
SMD_BAS_IP_HTR_16_[4]
AV:1804
Data Float
350
nvoHTR_16_5
inc count (9)
Output (non-polled)
31804
16
Inlet Temp
SMD_BAS_IP_HTR_16_[5]
AV:1805
Data Float
351
nvoHTR_16_6
inc count (9)
Output (non-polled)
31805
16
Exhaust Temp
SMD_BAS_IP_HTR_16_[6]
AV:1806
Data Float
352
nvoHTR_16_7
inc count (9)
Output (non-polled)
31806
16
Air Temp
SMD_BAS_IP_HTR_16_[7]
AV:1807
Data Float
353
nvoHTR_16_8
inc count (9)
Output (non-polled)
31807
16
Flame Strength
SMD_BAS_IP_HTR_16_[8]
AV:1808
Data Float
354
nvoHTR_16_9
inc count (9)
Output (non-polled)
31808
16
Fire Rate In
SMD_BAS_IP_HTR_16_[9]
AV:1809
Data Float
355
nvoHTR_16_10
inc count (9)
Output (non-polled)
31809
16
Fire Rate Out
SMD_BAS_IP_HTR_16_[10]
AV:1810
Data Float
356
nvoHTR_16_11
inc count (9)
Output (non-polled)
31810
16
Unit Type
SMD_BAS_IP_HTR_16_[11]
AV:1811
Data Float
357
nvoHTR_16_12
inc count (9)
Output (non-polled)
31811

Table of Contents