EasyManua.ls Logo

Watts Aerco ProtoNode FPC-N34 - Page 104

Watts Aerco ProtoNode FPC-N34
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 104 of 140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon SNVT
Lon Direction
Modbus
Address
16
Unit Size
SMD_BAS_IP_HTR_16_[12]
AV:1812
Data Float
358
nvoHTR_16_13
inc count (9)
Output (non-polled)
31812
16
Value State
SMD_BAS_IP_HTR_16_[13]
AV:1813
Data Float
359
nvoHTR_16_14
inc count (9)
Output (non-polled)
31813
16
Net Remote Setpt
SMD_BAS_IP_HTR_16_[14]
AV:1814
Data Float
360
nvoHTR_16_15
inc count (9)
Output (non-polled)
31814
16
Run Cycles Upper
SMD_BAS_IP_HTR_16_[15]
AV:1815
Data Float
361
nvoHTR_16_16
inc count (9)
Output (non-polled)
31815
16
Run Cycles Lower
SMD_BAS_IP_HTR_16_[16]
AV:1816
Data Float
362
nvoHTR_16_17
inc count (9)
Output (non-polled)
31816
16
Run Hours Upper
SMD_BAS_IP_HTR_16_[17]
AV:1817
Data Float
363
nvoHTR_16_18
inc count (9)
Output (non-polled)
31817
16
Run Hours Lower
SMD_BAS_IP_HTR_16_[18]
AV:1818
Data Float
364
nvoHTR_16_19
inc count (9)
Output (non-polled)
31818
16
Oxygen Level
SMD_BAS_IP_HTR_16_[19]
AV:1819
Data Float
365
nvoHTR_16_20
inc count (9)
Output (non-polled)
31819
Master Addr 247
Master Control Values
247
Write Cntrl Val to
BST/WHM
SMD_BAS_IP_Ctrl_[1]
* write "1" to
send Value to
WHM
AV:51
Data Float
2
nvoCtrl_2
inc count (9)
Input/Output
40051
247
BST/WHM Timeout
SMD_BAS_IP_Ctrl_[3]
**Read
Only**,
0=WHM
Present,
1=WHM
Absent
AV:53
Data Float
4
nvoCtrl_4
inc count (9)
Input/Output
40053
Read Master Operating Values
247
Mode
SMD_BAS_IP_OpVal_[0]
AV:100
Data Float
6
nvoOpVal_1
inc count (9)
Output (non-polled)
30100
247
Setpoint
SMD_BAS_IP_OpVal_[1]
AV:101
Data Float
7
nvoOpVal_2
inc count (9)
Output (non-polled)
30101
247
Setback Setpt
SMD_BAS_IP_OpVal_[2]
AV:102
Data Float
8
nvoOpVal_3
inc count (9)
Output (non-polled)
30102
247
Setback Start
SMD_BAS_IP_OpVal_[3]
AV:103
Data Float
9
nvoOpVal_4
inc count (9)
Output (non-polled)
30103
247
Setback End
SMD_BAS_IP_OpVal_[4]
AV:104
Data Float
10
nvoOpVal_5
inc count (9)
Output (non-polled)
30104
247
Auto Master
SMD_BAS_IP_OpVal_[5]
AV:105
Data Float
11
nvoOpVal_6
inc count (9)
Output (non-polled)
30105
247
Avg Outlet Temp
SMD_BAS_IP_OpVal_[6]
AV:106
Data Float
12
nvoOpVal_7
inc count (9)
Output (non-polled)
30106

Table of Contents