EasyManua.ls Logo

Watts Aerco ProtoNode FPC-N34 - Page 105

Watts Aerco ProtoNode FPC-N34
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 105 of 140
247
Units Active
SMD_BAS_IP_OpVal_[7]
AV:107
Data Float
13
nvoOpVal_8
inc count (9)
Output (non-polled)
30107
247
Units Faulted
SMD_BAS_IP_OpVal_[8]
AV:108
Data Float
14
nvoOpVal_9
inc count (9)
Output (non-polled)
30108
247
Master Addr
SMD_BAS_IP_OpVal_[9]
AV:109
Data Float
15
nvoOpVal_10
inc count (9)
Output (non-polled)
30109
247
Header Temp
SMD_BAS_IP_OpVal_[10]
AV:110
Data Float
16
nvoOpVal_11
inc count (9)
Output (non-polled)
30110
247
Outdoor Temp
SMD_BAS_IP_OpVal_[11]
AV:111
Data Float
17
nvoOpVal_12
inc count (9)
Output (non-polled)
30111
247
Percent Output
SMD_BAS_IP_OpVal_[12]
AV:112
Data Float
18
nvoOpVal_13
inc count (9)
Output (non-polled)
30112
247
Number of Units
Firing
SMD_BAS_IP_OpVal_[13]
AV:113
Data Float
19
nvoOpVal_14
inc count (9)
Output (non-polled)
30113
247
Master Active
Setpoint
SMD_BAS_IP_OpVal_[14]
AV:114
Data Float
20
nvoOpVal_15
inc count (9)
Output (non-polled)
30114
247
Next Turn-On
Percent
SMD_BAS_IP_OpVal_[15]
AV:115
Data Float
21
nvoOpVal_16
inc count (9)
Output (non-polled)
30115
247
Header High Limit
SMD_BAS_IP_OpVal_[16]
AV:116
Data Float
22
nvoOpVal_17
inc count (9)
Output (non-polled)
30116
247
Header Low Limit
SMD_BAS_IP_OpVal_[17]
AV:117
Data Float
23
nvoOpVal_18
inc count (9)
Output (non-polled)
30117
247
Header Temp High
Limit
SMD_BAS_IP_OpVal_[18]
AV:118
Data Float
24
nvoOpVal_19
inc count (9)
Output (non-polled)
30118
247
Header Setpoint
Mode
SMD_BAS_IP_OpVal_[19]
AV:119
Data Float
25
nvoOpVal_20
inc count (9)
Output (non-polled)
30119
Write Master Operating Values
247
Setpt
SMD_BAS_IP_CtrlVal_[0]
AV:200
Data Float
26
nvoCtrlVal_1
inc count (9)
Input (non-polling)
40200
247
Setback Setpt
SMD_BAS_IP_CtrlVal_[1]
AV:201
Data Float
27
nvoCtrlVal_2
inc count (9)
Input (non-polling)
40201
247
Setback Start
SMD_BAS_IP_CtrlVal_[2]
AV:202
Data Float
28
nvoCtrlVal_3
inc count (9)
Input (non-polling)
40202
247
Setback End
SMD_BAS_IP_CtrlVal_[3]
AV:203
Data Float
29
nvoCtrlVal_4
inc count (9)
Input (non-polling)
40203
* NOTE:
Writing a setpoint to WHM or BST is a two-step process. First write the setpoint to the “Write Setpoint” address. Next, write a “1” to the
“Write Control” address. This will cause the ProtoNode to send the setpoint to the master C-More. After the setpoint is sent, this address
value will change to “0” when read.