APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 95 of 140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon SNVT
Lon Direction
Modbus
Address
6
Unit Type
SMD_BAS_IP_HTR_06_[11]
AV:811
Data Float
157
nvoHTR_06_12
inc count (9)
Output (non-polled)
30811
6
Unit Size
SMD_BAS_IP_HTR_06_[12]
AV:812
Data Float
158
nvoHTR_06_13
inc count (9)
Output (non-polled)
30812
6
Value State
SMD_BAS_IP_HTR_06_[13]
AV:813
Data Float
159
nvoHTR_06_14
inc count (9)
Output (non-polled)
30813
6
Net Remote Setpt
SMD_BAS_IP_HTR_06_[14]
AV:814
Data Float
160
nvoHTR_06_15
inc count (9)
Output (non-polled)
30814
6
Run Cycles Upper
SMD_BAS_IP_HTR_06_[15]
AV:815
Data Float
161
nvoHTR_06_16
inc count (9)
Output (non-polled)
30815
6
Run Cycles Lower
SMD_BAS_IP_HTR_06_[16]
AV:816
Data Float
162
nvoHTR_06_17
inc count (9)
Output (non-polled)
30816
6
Run Hours Upper
SMD_BAS_IP_HTR_06_[17]
AV:817
Data Float
163
nvoHTR_06_18
inc count (9)
Output (non-polled)
30817
6
Run Hours Lower
SMD_BAS_IP_HTR_06_[18]
AV:818
Data Float
164
nvoHTR_06_19
inc count (9)
Output (non-polled)
30818
6
Oxygen Level
SMD_BAS_IP_HTR_06_[19]
AV:819
Data Float
165
nvoHTR_06_20
inc count (9)
Output (non-polled)
30819
Blr Addr 7
7
Comm Address
SMD_BAS_IP_HTR_07_[0]
AV:900
Data Float
166
nvoHTR_07_1
inc count (9)
Output (non-polled)
30900
7
Unit Status
SMD_BAS_IP_HTR_07_[1]
AV:901
Data Float
167
nvoHTR_07_2
inc count (9)
Output (non-polled)
30901
7
Fault Code
SMD_BAS_IP_HTR_07_[2]
AV:902
Data Float
168
nvoHTR_07_3
inc count (9)
Output (non-polled)
30902
7
Outlet Temp
SMD_BAS_IP_HTR_07_[3]
AV:903
Data Float
169
nvoHTR_07_4
inc count (9)
Output (non-polled)
30903
7
FFWD Temp
SMD_BAS_IP_HTR_07_[4]
AV:904
Data Float
170
nvoHTR_07_5
inc count (9)
Output (non-polled)
30904
7
Inlet Temp
SMD_BAS_IP_HTR_07_[5]
AV:905
Data Float
171
nvoHTR_07_6
inc count (9)
Output (non-polled)
30905
7
Exhaust Temp
SMD_BAS_IP_HTR_07_[6]
AV:906
Data Float
172
nvoHTR_07_7
inc count (9)
Output (non-polled)
30906
7
Air Temp
SMD_BAS_IP_HTR_07_[7]
AV:907
Data Float
173
nvoHTR_07_8
inc count (9)
Output (non-polled)
30907
7
Flame Strength
SMD_BAS_IP_HTR_07_[8]
AV:908
Data Float
174
nvoHTR_07_9
inc count (9)
Output (non-polled)
30908
7
Fire Rate In
SMD_BAS_IP_HTR_07_[9]
AV:909
Data Float
175
nvoHTR_07_10
inc count (9)
Output (non-polled)
30909
7
Fire Rate Out
SMD_BAS_IP_HTR_07_[10]
AV:910
Data Float
176
nvoHTR_07_11
inc count (9)
Output (non-polled)
30910
7
Unit Type
SMD_BAS_IP_HTR_07_[11]
AV:911
Data Float
177
nvoHTR_07_12
inc count (9)
Output (non-polled)
30911
7
Unit Size
SMD_BAS_IP_HTR_07_[12]
AV:912
Data Float
178
nvoHTR_07_13
inc count (9)
Output (non-polled)
30912
7
Value State
SMD_BAS_IP_HTR_07_[13]
AV:913
Data Float
179
nvoHTR_07_14
inc count (9)
Output (non-polled)
30913

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts Aerco ProtoNode FPC-N34 and is the answer not in the manual?

Watts Aerco ProtoNode FPC-N34 Specifications

General IconGeneral
BrandWatts
ModelAerco ProtoNode FPC-N34
CategoryGateway
LanguageEnglish