EasyManuals Logo

Watts Aerco ProtoNode FPC-N34 User Manual

Watts Aerco ProtoNode FPC-N34
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 96 of 140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon SNVT
Lon Direction
Modbus
Address
7
Net Remote Setpt
SMD_BAS_IP_HTR_07_[14]
AV:914
Data Float
180
nvoHTR_07_15
inc count (9)
Output (non-polled)
30914
7
Run Cycles Upper
SMD_BAS_IP_HTR_07_[15]
AV:915
Data Float
181
nvoHTR_07_16
inc count (9)
Output (non-polled)
30915
7
Run Cycles Lower
SMD_BAS_IP_HTR_07_[16]
AV:916
Data Float
182
nvoHTR_07_17
inc count (9)
Output (non-polled)
30916
7
Run Hours Upper
SMD_BAS_IP_HTR_07_[17]
AV:917
Data Float
183
nvoHTR_07_18
inc count (9)
Output (non-polled)
30917
7
Run Hours Lower
SMD_BAS_IP_HTR_07_[18]
AV:918
Data Float
184
nvoHTR_07_19
inc count (9)
Output (non-polled)
30918
7
Oxygen Level
SMD_BAS_IP_HTR_07_[19]
AV:919
Data Float
185
nvoHTR_07_20
inc count (9)
Output (non-polled)
30919
Blr Addr 8
8
Comm Address
SMD_BAS_IP_HTR_08_[0]
AV:1000
Data Float
186
nvoHTR_08_1
inc count (9)
Output (non-polled)
31000
8
Unit Status
SMD_BAS_IP_HTR_08_[1]
AV:1001
Data Float
187
nvoHTR_08_2
inc count (9)
Output (non-polled)
31001
8
Fault Code
SMD_BAS_IP_HTR_08_[2]
AV:1002
Data Float
188
nvoHTR_08_3
inc count (9)
Output (non-polled)
31002
8
Outlet Temp
SMD_BAS_IP_HTR_08_[3]
AV:1003
Data Float
189
nvoHTR_08_4
inc count (9)
Output (non-polled)
31003
8
FFWD Temp
SMD_BAS_IP_HTR_08_[4]
AV:1004
Data Float
190
nvoHTR_08_5
inc count (9)
Output (non-polled)
31004
8
Inlet Temp
SMD_BAS_IP_HTR_08_[5]
AV:1005
Data Float
191
nvoHTR_08_6
inc count (9)
Output (non-polled)
31005
8
Exhaust Temp
SMD_BAS_IP_HTR_08_[6]
AV:1006
Data Float
192
nvoHTR_08_7
inc count (9)
Output (non-polled)
31006
8
Air Temp
SMD_BAS_IP_HTR_08_[7]
AV:1007
Data Float
193
nvoHTR_08_8
inc count (9)
Output (non-polled)
31007
8
Flame Strength
SMD_BAS_IP_HTR_08_[8]
AV:1008
Data Float
194
nvoHTR_08_9
inc count (9)
Output (non-polled)
31008
8
Fire Rate In
SMD_BAS_IP_HTR_08_[9]
AV:1009
Data Float
195
nvoHTR_08_10
inc count (9)
Output (non-polled)
31009
8
Fire Rate Out
SMD_BAS_IP_HTR_08_[10]
AV:1010
Data Float
196
nvoHTR_08_11
inc count (9)
Output (non-polled)
31010
8
Unit Type
SMD_BAS_IP_HTR_08_[11]
AV:1011
Data Float
197
nvoHTR_08_12
inc count (9)
Output (non-polled)
31011
8
Unit Size
SMD_BAS_IP_HTR_08_[12]
AV:1012
Data Float
198
nvoHTR_08_13
inc count (9)
Output (non-polled)
31012
8
Value State
SMD_BAS_IP_HTR_08_[13]
AV:1013
Data Float
199
nvoHTR_08_14
inc count (9)
Output (non-polled)
31013
8
Net Remote Setpt
SMD_BAS_IP_HTR_08_[14]
AV:1014
Data Float
200
nvoHTR_08_15
inc count (9)
Output (non-polled)
31014
8
Run Cycles Upper
SMD_BAS_IP_HTR_08_[15]
AV:1015
Data Float
201
nvoHTR_08_16
inc count (9)
Output (non-polled)
31015
8
Run Cycles Lower
SMD_BAS_IP_HTR_08_[16]
AV:1016
Data Float
202
nvoHTR_08_17
inc count (9)
Output (non-polled)
31016

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts Aerco ProtoNode FPC-N34 and is the answer not in the manual?

Watts Aerco ProtoNode FPC-N34 Specifications

General IconGeneral
BrandWatts
ModelAerco ProtoNode FPC-N34
CategoryGateway
LanguageEnglish