5
DETAILED PARAMETER DESCRIPTION
The parameter P0214, being active, controls the following faults and alarms:
A0301: Input undervoltage.
A0302: Input overvoltage.
F0303: Input undervoltage.
F0304: Input overvoltage.
F0305: Input unbalance/phase loss.
The phase-loss detector is enabled to act when:
1. P0214 = Active.
2. Inverter enabled.
3. Pre-charge completed.
4. No Ride-through.
Table 5.25: Line phase loss detection
P0214 Function
0
Inactive
1
Active
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0220 - LOCAL/REMOTE selection source
Adjustable range: 0 to 12 Factory setting: 11
Acesso: Menu → Configurations → Commands → Local
Description:
It defines the origin of the command that will select between the Local situation and the Remote situation.
Table 5.26: LOCAL/REMOTE selection source
P0220 Function
0
Always LOCAL
1
Always REMOTE
2
HMI
key (LOCAL default)
3
HMI
key (REMOTE default)
4
Digital Inputs DI2...DI10 (P0264...P0272)
5
Serial (LOCAL Default)
6
Serial (REMOTE Default)
7
Fieldbus (LOCAL Default)
8
Fieldbus (REMOTE Default)
9
LOCAL PLC
10
REMOTE PLC
11
Graphic HMI
key (LOCAL Default)
12
Graphic HMI
key (REMOTE Default)
✓
NOTE!
This parameter can be changed only with the motor stopped.
MVW3000 | 5-35