30
83055116 • 1/2016-05
Installation and Operating Instructions
G
as burner WG20.../1-C ZM-LN (W-FM 25)
5 Operation
5
.3 Linearization
During commissioning, it is possible to carry out the linearization of the operating points
in gas operation.
During linearization, a straight line is generated from the operating point displayed, to
P9. The values on the straight line are adopted as the new operating points.
Initiate a calculation after P9
u Press [Enter].
a The combustion manager changes to linearization mode.
The linearization mode can be interrupted by pressing the [-] key.
u Confirm with [+] key.
a Linearization is initiated.
Example:
1 Calculation from P1 to P9
2 Calculation from P5 to P9
P1 P2 P3 P4 P5 P6 P7 P8 P9 P1 P2 P3 P4 P5 P6 P7 P8 P9
1 2