45
6 Commissioning and startup
6
.7 Subsequent optimization of the operating points
For safe and economic operation of the plant, the combustion values can subsequently
be corrected.
u Unplug the bridging plug No. 7 from the combustion manager.
a The combustion manager drives to stand-by.
u Briefly press [-] and [+] keys simultaneously.
aThe combustion manager changes to access level.
u Press [+].
aThe combustion manager changes to setting level.
u Plug the bridging plug No. 7 on the combustion manager.
a The burner starts and stops in operating point P0 (ignition position).
u Move through the other operating points using the [+] and [-] keys and optimize, if
necessary.
Exit setting level
u Press [G] and [L/A] simultaneously.
a The upper operating limit (bo) is displayed.
u Press [G] and [L/A] simultaneously.
a The lower operating limit is displayed (bu).
u Press [G] and [L/A] simultaneously.
a The combustion manager changes to operating level.
Installation and Operating Instructions
G
as burner WG20.../1-C ZM-LN (W-FM 25)
83055116 • 1/2016-05