Universal Pressure Transmitter UniTrans
Technical Data
Subject to change due to technical modifications. © Copyright WIKA Alexander Wiegand GmbH & Co. KG / BRD
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg ·
(09372) 132 - 710 · Fax - 706 · E-mail: support-tronic@wika.de · www.wika.de
50
3 Technical Data
3.1 Input-values
3.2 Output-values
Pressure Ran
es
(Absolute pressure upon request)
/ overpressure limit / burst pressure
0 ... 0.4 bar 2 2.4
0 ... 1,6 bar 10 12
0 ... 6 bar 35 42
0 ... 16 bar 80 96
0 ... 40 bar 80 400
0 ... 100 bar 200 800
0 ... 250 bar 500 1200
0 ... 600 bar 1200 2400
1)
0 ... 1.000 bar 1500 3000
0 ... 1,600 bar 2000 4000
0 ... 2,500 bar 3000 5000
0 ... 4,000 bar 4400 7000
-1 ... +0 bar* 2 2.4
-1 ... +0,6 bar* 10 12
-1 ... +3 bar* 35 42
-1 ... +5 bar* 35 42
-1 ... +15 bar* 80 96
*onl
relative pressure
Do not exceed the nominal pressure!
1)For flush diaphragm version: The value specified in the table
applies only when sealing is realised with the sealing ring under-
neath the hex. Otherwise max. 1500 bar applies.
Output si
es < 1000 bar
<
0.30 at ran
es > 1000 bar
Turn down behavior: (1/k)
up to 1 : 5
1 : 5 to 1 : 20
no chan
es of deviation
the accurac
the
factor (turn down / 5)
example for TD = 1:15, (k = 15)
accurac
= 0.10 * (15/5) = 0.3
Overall deviation
(at +10 °C ... +40 °C)
<
0.15 % (limit point calibration)
< 0.6 % for pressure ran
es of > 1000
bar
Load R
A
< (U
B
–12 V)/0.023 A
with R
A
in Ohm and U
B
in Volt
Fault si