INSTALLATION English
Installation and operating instructions Wilo EHV G2 - DN250 35
5.2.2. Fastening with HAS... / HIS anchor bolts
• These anchors may only be used in reinforced or unreinforced normal concrete with
astrengthclassofbetweenC20/25andC50/60(accordingtoEN206:2000-12).
• The anchor bolts are only suitable for crack-free concrete. Optionally, anchor bolts are
also available for cracked concrete.
• The foundation for the anchors should be dry.
• Before using the anchor bolts, the strength of the structure must be ascertained in order
to ensure that the reaction forces can be absorbed.
• Take care not to damage the grout cartridge during transport, as otherwise the adhesive
cement will harden.
• Do not use defective or old grout cartridges (see the use-by date).
• Groutcartridgesmayonlybestoredbetween+5°Cand+25°C.Theymustbestored
inacool,dryanddarkplace.
• Hazard labeling on grout cartridges
CAUTION – irritant substances!
The grout cartridges contain dibenzoyl peroxide. This substance is an irritant!
• R36/38 – causes eye and skin irritation
• R43 – may cause sensitization by skin contact
• S37/39 – wear suitable protective clothing when working
• S26 – in case of contact with eyes, rinse thoroughly with water and seek
medical advice
• S28 – after contact with skin, wash immediately with water and plenty
Type
Rod
length
Drill hole
depth
Drill hole
diameter
Minimum
distance
to edge
Minimum
foundation
thickness
Tightening
torque
Maximum
component
thickness
HAS-R M8x80/14 110 mm 80 mm 10 mm 100 mm 130 mm 10 Nm 14 mm
HAS-R M12x110/28 160 mm 110 mm 14 mm 135 mm 160 mm 40 Nm 28 mm
HAS-R M16x125/38 190 mm 125 mm 18 mm 155 mm 175 mm 80 Nm 38 mm
HAS-R M16x125/108 260 mm 125 mm 18 mm 155 mm 175 mm 80 Nm 108 mm
HAS-E-R M20x170/48 240 mm 170 mm 24 mm 210 mm 220 mm 150 Nm 48 mm*
HAS-E-R M24x210/54 290 mm 210 mm 28 mm 260 mm 260 mm 200 Nm 54 mm*
HIS-RN M16x170 170 mm 170 mm 28 mm 210 mm 220 mm 80 Nm **
W-FA 10/15/85 85 mm 70 mm 10 mm 65 mm 100 mm 30 Nm 10 mm
*Withoutexternalhexhead
** M16 female thread